Title :
Arcing phenomena and their application for fault location in SF6-insulated equipment
Author :
Ushida, K. ; Takagi, I. ; Maruyama, S. ; Sakakibara, T. ; Kamata, I.
Author_Institution :
Chubu Electr. Power Co., Nagoya, Japan
fDate :
7/1/1989 12:00:00 AM
Abstract :
A system is presented for locating faults by measuring time lags in the propagation of gas pressure shock waves caused by ground faults in GIS (gas-insulated substation) and GIB (gas-insulated bus) equipment. For sensors, the system uses shock gas pressure relays of an optical signal transmission type. It is well designed, with few sensors, to locate faults with high accuracy. Also presented are results of an extensive arc test conducted on actual equipment when developing the system, and some applications of the system in substations are described
Keywords :
arcs (electric); electric sensing devices; fault location; gaseous insulation; substations; sulphur compounds; GIB; GIS; fault location; gas-insulated buses; gas-insulated substation; optical signal transmission shock gas pressure relays; Fault location; Gas detectors; Geographic Information Systems; Optical propagation; Optical sensors; Pressure measurement; Sensor phenomena and characterization; Shock waves; Substations; Time measurement;
Journal_Title :
Power Delivery, IEEE Transactions on