DocumentCode
1184695
Title
High-Voltage on-Site Commissioning Tests for Gas-Insulated Substations Using UHF Partial Discharge Detection
Author
Bell, R. ; Charlson, C. ; Halliday, S. ; Irwin, T. ; Lopez-Roldan, Jose ; Nixon, J.
Author_Institution
VA Tech Reyrolle
Volume
22
Issue
6
fYear
2002
fDate
6/1/2002 12:00:00 AM
Firstpage
61
Lastpage
61
Abstract
This paper describes the practical application of the UHF Partial Discharge Detection method that VA TECH Reyrolle has routinely applied to high-voltage on-site commissioning tests on gas-insulated substations (GIS) for over 10 years. The location of the partial discharge (PD) sensors has a significant effect on the sensitivity of the UHF method. Research has been undertaken to quantify the parameters that affect this, i.e., attenuation, GIS geometry, etc. Verifying the correct operation of the detection system and its sensitivity is a crucial step in preparing for an HV test. In order to do this, special test equipment has been developed to ensure that all of the cabling, connections, etc. attached to the detection equipment are correct and the detection level of the couplers confirmed. The paper discusses IEC 60517 (general guidelines for GIS HV testing), its most usual interpretation, and how the application of the UHF technique can transform this interpretation.
Keywords
Attenuation; Computational geometry; Couplers; Geographic Information Systems; Guidelines; IEC standards; Partial discharges; Substations; System testing; Test equipment; Partial discharge; Substation commissioning test; UHF; gas insulated substations (GIS); high-voltage testing;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312306
Filename
4312306
Link To Document