    Dynamic Behavior of Metal Enclosures for Gas Insulated Substations During Ground Faults and Their Immediate Location by Mechanical Means

  • Author

    Tominaga, Shotaro ; Okutsu, Naohiro ; Mukae, Hisao ; Takahas, Yasuhide ; Matsuda, Setuyuki

  • Author_Institution
    Mitsubishi Electric Corporation Itami Works
  • Issue
    4
  • fYear
    1979
  • fDate
    7/1/1979 12:00:00 AM
  • Firstpage
    1283
  • Lastpage
    1290
  • Abstract
    Techniques to locate and indicate faulted gas sections are needed in the event of ground faults of SF6 gas insulated equipment, especially of gas insulated substations (GIS) and gas insulated buses (GIB). The authors have developed mechanical sensors operating on shock acceleration by making use of the dynamic characteristics of the tanks, which are components of the above equipment. The theoretical and experimental descriptions of the process and the results of the development are introduced.
  • Keywords
    Acceleration; Circuit faults; Costs; Dielectrics and electrical insulation; Electric shock; Fault detection; Gas detectors; Gas insulation; Mechanical sensors; Substations;