DocumentCode :
1185029
Title :
A simplified lumped parameter model for finding distribution transformer and secondary system responses to lightning
Author :
Smith, D.R. ; Puri, J.L.
Author_Institution :
Westinghouse Electr. Corp., Pittsburgh, PA, USA
Volume :
4
Issue :
3
fYear :
1989
fDate :
7/1/1989 12:00:00 AM
Firstpage :
1927
Lastpage :
1936
Abstract :
The results of other investigations on distribution transformer and system response to lightning strokes to the primary terminal of the transformer are briefly reviewed, from the standpoint of system and transformer currents, and service entrance phase-to-neutral voltage. A simplified lumped parameter model for the transformer and associated distribution system is described. The analysis of this model yields equations for the quantitative determination of the influence of system parameters on the lightning-induced surge currents in distribution transformers, and the service entrance phase-to-neutral voltages
Keywords :
lightning; power transformers; surges; distribution transformer; lightning response; lightning strokes; lightning-induced surge currents; lumped parameter model; service entrance phase-to-neutral voltage; transformer currents; Arresters; Automatic testing; Conductors; EMTP; Equations; Impedance; Inductance; Lightning; Surges; System testing;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.32692
Filename :
32692
Link To Document :
بازگشت