Abstract :
The combined effects of fault resistance and load flow cause the apparent impedance for ground faults to vary over a wide range. A new ground distance relay using a four input phase comparator provides improved security with a fault resistance capability similar to that of a simple quadrature polarized ground distance relay.
Keywords :
Electric resistance; Impedance; Load flow; Polarization; Power system relaying; Protective relaying; Relays; Security; TV; Voltage;