Title :
Design Considerations in the Development of a New Ground Distance Relay
Author :
Wilkinson, S.B. ; Mathews, C.A. ; Keeney, M.F.
Author_Institution :
General Electric Company
Abstract :
The combined effects of fault resistance and load flow cause the apparent impedance for ground faults to vary over a wide range. A new ground distance relay using a four input phase comparator provides improved security with a fault resistance capability similar to that of a simple quadrature polarized ground distance relay.
Keywords :
Electric resistance; Impedance; Load flow; Polarization; Power system relaying; Protective relaying; Relays; Security; TV; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1979.319471