• DocumentCode
    1185395
  • Title

    Watthour Meter Accuracy on Integral-Cycle-Controlled Resistance Loads

  • Author

    Emanuel, A.E. ; Hynds, B.M. ; Levitsky, F.J.

  • Author_Institution
    Worcester Polytechnic Institute
  • Issue
    5
  • fYear
    1979
  • Firstpage
    1583
  • Lastpage
    1590
  • Abstract
    The change in performance of induction watthour meters when measuring integral-cycle-controlled resistance loads was studied. A simple mathematical model is used to explain the main cause for error. Test results for representative meters show that meters on integral cycle speed up, resulting in substantial positive errors. When mixed loads are monitored, the error becomes small and within commercially acceptable limits.
  • Keywords
    Circuit testing; Electrical resistance measurement; Error correction; Power conditioning; Steady-state; Switches; Thyristors; Velocity measurement; Voltage; Watthour meters;