DocumentCode
1185455
Title
Performance of Insulators Covered With Snow or Ice
Author
Fujimura, Tetsuo ; Naito, Katsuhiko ; Hasegawa, Yoshio ; Kawaguchi, Toshiyuki
Author_Institution
NGK INSULATORS, LTD.
Issue
5
fYear
1979
Firstpage
1621
Lastpage
1631
Abstract
This paper describes the results of investigation made into the performance of insulators covered with snow or ice. The AC and DC withstand voltages of snow-covered insulators were characterized by the conductivity of water melted from the snow. The AC withstand voltage of ice-coated insulators was characterized by the length of icicles and conductivity of the water melted from the ice. And the switching impulse flashover voltage of snow-covered insulator strings was almost proportional to gap length between the arcing horns or the insulator strings. Flashover voltage of a 75% snow-covered insulator string, which means the worst case, was 40 ¿65% of the positive wet flashover voltage of the clean insulator string.
Keywords
Contamination; Flashover; Ice; Impulse testing; Insulation; Insulator testing; Life testing; Power transmission lines; Snow; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1979.319479