• DocumentCode
    1185455
  • Title

    Performance of Insulators Covered With Snow or Ice

  • Author

    Fujimura, Tetsuo ; Naito, Katsuhiko ; Hasegawa, Yoshio ; Kawaguchi, Toshiyuki

  • Author_Institution
    NGK INSULATORS, LTD.
  • Issue
    5
  • fYear
    1979
  • Firstpage
    1621
  • Lastpage
    1631
  • Abstract
    This paper describes the results of investigation made into the performance of insulators covered with snow or ice. The AC and DC withstand voltages of snow-covered insulators were characterized by the conductivity of water melted from the snow. The AC withstand voltage of ice-coated insulators was characterized by the length of icicles and conductivity of the water melted from the ice. And the switching impulse flashover voltage of snow-covered insulator strings was almost proportional to gap length between the arcing horns or the insulator strings. Flashover voltage of a 75% snow-covered insulator string, which means the worst case, was 40 ¿65% of the positive wet flashover voltage of the clean insulator string.
  • Keywords
    Contamination; Flashover; Ice; Impulse testing; Insulation; Insulator testing; Life testing; Power transmission lines; Snow; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319479
  • Filename
    4113669