• DocumentCode
    1185728
  • Title

    Diagnostic Methods in Revealing Internal Moisture in Polymer Housed Metal Oxide Surge Arresters

  • Author

    Lahti, K. ; Kannus, K. ; Nousianen, K.

  • Author_Institution
    Tampere University of Technology
  • Volume
    22
  • Issue
    7
  • fYear
    2002
  • fDate
    7/1/2002 12:00:00 AM
  • Firstpage
    61
  • Lastpage
    61
  • Abstract
    Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect ageing and degradation of metal oxide material. The suitability of different methods for revealing intemal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5 year laboratory test series conducted for six different types of polymer housed distribution class arresters. AC power losses, third harmonic content of resistive leakage current, DC leakage current and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with intemal moisture are also studied. AC power loss and DC leakage current measurements were found to be good methods, while the other two can only be used as additional methods when diagnosing intemal moisture in polymer housed arresters.
  • Keywords
    Aging; Arresters; Degradation; Leakage current; Moisture measurement; Partial discharge measurement; Performance evaluation; Polymers; Surges; Testing; Arresters; degradation; insulation; leak detection; moisture; partial discharges; polymers;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312422
  • Filename