DocumentCode
1185728
Title
Diagnostic Methods in Revealing Internal Moisture in Polymer Housed Metal Oxide Surge Arresters
Author
Lahti, K. ; Kannus, K. ; Nousianen, K.
Author_Institution
Tampere University of Technology
Volume
22
Issue
7
fYear
2002
fDate
7/1/2002 12:00:00 AM
Firstpage
61
Lastpage
61
Abstract
Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect ageing and degradation of metal oxide material. The suitability of different methods for revealing intemal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5 year laboratory test series conducted for six different types of polymer housed distribution class arresters. AC power losses, third harmonic content of resistive leakage current, DC leakage current and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with intemal moisture are also studied. AC power loss and DC leakage current measurements were found to be good methods, while the other two can only be used as additional methods when diagnosing intemal moisture in polymer housed arresters.
Keywords
Aging; Arresters; Degradation; Leakage current; Moisture measurement; Partial discharge measurement; Performance evaluation; Polymers; Surges; Testing; Arresters; degradation; insulation; leak detection; moisture; partial discharges; polymers;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312422
Filename
4312422
Link To Document