• DocumentCode
    1186020
  • Title

    Grounding System Tests for Analysis of Fault-Induced Voltages on Communication Cables

  • Author

    Dick, E.P. ; Erven, C.C. ; Harvey, S.M.

  • Author_Institution
    Ontario Hydro
  • Issue
    6
  • fYear
    1979
  • Firstpage
    2115
  • Lastpage
    2125
  • Abstract
    To avoid failures of communication lines serving electric power stations during line-to-ground faults, an analysis of the expected voltages must be carried out for each projected station. A method for predicting reliable results without conducting staged-fault tests is described. The technique uses ac current injection at 5 to 10 Hz away from the power-system frequency to simulate a fault condition, and a sensitive detection scheme for measuring the amplitude and phase of secondary voltages and currents in the presence of power-system interference. The method is employed to predict voltage stresses on communication cables in a large multi-station power-system complex.
  • Keywords
    Communication cables; Current measurement; Failure analysis; Fault detection; Grounding; Phase detection; Phase frequency detector; Power system reliability; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319411
  • Filename
    4113729