• DocumentCode
    1186172
  • Title

    Stability of a Hydraulic Turbine Generating Unit Controlled by P.I.D. Governor

  • Author

    Hagihara, S. ; Yokota, H. ; Goda, K. ; Isobe, K.

  • Author_Institution
    Central Research Laboratory, Mitsubishi Electric Corporation
  • Issue
    6
  • fYear
    1979
  • Firstpage
    2294
  • Lastpage
    2298
  • Abstract
    The effect of derivative gain and other governor parameters on the stability boundaries of a hydraulic turbine generating unit supplying an isolated load is investigated. Root locus method is used for analysis of the effect of governor parameters on the dynamic behavior of the hydroelectric power system. A general guide for optimum adjustment of derivative gain and other parameters is provided.
  • Keywords
    Electrical equipment industry; Electricity supply industry; Hydraulic turbines; Hydroelectric power generation; Laplace equations; Power generation; Power system analysis computing; Power system dynamics; Power system stability; Transfer functions;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1979.319429
  • Filename
    4113747