Current Transformer Accuracy on Asymmetrically Triggered Thyristorized Circuits
Author
Chandra, H.N. ; Emanuel, A.E. ; Levitsky, F.J.
Author_Institution
Worcester Polytechnic Institute
Issue
1
fYear
1980
Firstpage
92
Lastpage
98
Abstract
This work presents the steady-state performance of a metering-type current transformer used in circuits with asymmetrically triggered silicon-controlled rectifiers or triacs. It was found that minute differences between the triggering angles generate sufficient dc bias of the magnetic core to impair the accuracy of the transformer.
Keywords
Circuit testing; Current measurement; Current transformers; DC generators; Phase measurement; Potentiometers; Shape; Steady-state; Thyristors; Voltage;