• DocumentCode
    1186594
  • Title

    Estimating Overpressures in Pole-Type Distribution Transformers, Part I: Tank Withstand Evaluation

  • Author

    Hamel, A. ; Dastous, J. B. ; Foata, Marc

  • Author_Institution
    Hydro-Quebec; Hydro-Quebec/IREQ
  • Volume
    22
  • Issue
    8
  • fYear
    2002
  • Firstpage
    70
  • Lastpage
    70
  • Abstract
    When an electric arc is generated in transformer oil, a strong overpressure may rapidly develop in the tank, especially for low-impedance faults. This paper presents the test method and results obtained in a project aimed at assessing the human and environmental risks associated with this type of fault. Limit energy and pressure values were defined in terms of different safety levels. The best means of limiting the energy and pressure at a safety level in the transformer tank during internal faults greater than 1.7 kA is to protect the transformer with a current-limiting fuse. Other means to increase the mechanical withstand of transformer tanks under such faults are also discussed.
  • Keywords
    Aging; Arc discharges; Dielectrics and electrical insulation; Fuses; Oil insulation; Power harmonic filters; Power transformer insulation; Protection; Safety; Testing; Transformers; arc discharge; fault current; fuse; protection; safety; test pressure;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312520
  • Filename
    4312520