DocumentCode
1186603
Title
Estimating Overpressures in Pole-Type Distribution Transformers, Part II: Prediction Tools
Author
Dastous, J. B. ; Hamel, A. ; Foata, Marc
Author_Institution
Hydro-Quebec/IREQ; Hydro-Quebec
Volume
22
Issue
8
fYear
2002
Firstpage
70
Lastpage
70
Abstract
Low-impedance faults are difficult to contain from the point of view of cover retention and tank rupture in pole-type distribution transformers. Evaluation of a transformer´s containment capabilities needs to consider two aspects: the overpressure caused by an arc of given parameters and the pressure withstand of the tank. This paper presents two methods to calculate overpressures as a function of the arc and all the relevant geometrical parameters: tank diameter, air space height, and the depth of the arc below the oil. Both methods have been validated with experiments. Results of tests to determine the pressure withstand of typical tanks are presented. It was found that an average value of the overpressure withstand capability is around 100 kPa. For a given tank geometry and fault parameters, a current-limiting fuse would be reqwred if the methods proposed here predict an overpressure over 100 kPa.
Keywords
Aging; Arc discharges; Dielectrics and electrical insulation; Fuses; Oil insulation; Power harmonic filters; Power transformer insulation; Protection; Safety; Testing; Arc discharges; explosions; finite difference methods; prediction methods; pressure effects; transformers;