• DocumentCode
    1186603
  • Title

    Estimating Overpressures in Pole-Type Distribution Transformers, Part II: Prediction Tools

  • Author

    Dastous, J. B. ; Hamel, A. ; Foata, Marc

  • Author_Institution
    Hydro-Quebec/IREQ; Hydro-Quebec
  • Volume
    22
  • Issue
    8
  • fYear
    2002
  • Firstpage
    70
  • Lastpage
    70
  • Abstract
    Low-impedance faults are difficult to contain from the point of view of cover retention and tank rupture in pole-type distribution transformers. Evaluation of a transformer´s containment capabilities needs to consider two aspects: the overpressure caused by an arc of given parameters and the pressure withstand of the tank. This paper presents two methods to calculate overpressures as a function of the arc and all the relevant geometrical parameters: tank diameter, air space height, and the depth of the arc below the oil. Both methods have been validated with experiments. Results of tests to determine the pressure withstand of typical tanks are presented. It was found that an average value of the overpressure withstand capability is around 100 kPa. For a given tank geometry and fault parameters, a current-limiting fuse would be reqwred if the methods proposed here predict an overpressure over 100 kPa.
  • Keywords
    Aging; Arc discharges; Dielectrics and electrical insulation; Fuses; Oil insulation; Power harmonic filters; Power transformer insulation; Protection; Safety; Testing; Arc discharges; explosions; finite difference methods; prediction methods; pressure effects; transformers;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312521
  • Filename
    4312521