DocumentCode
1186621
Title
Experience with Return Voltage Measurements for Assessing Insulation Conditions in Service Aged Transformers
Author
Saha, Tapan Kumar ; Yao, Z. T.
Author_Institution
University of Queensland
Volume
22
Issue
8
fYear
2002
Firstpage
70
Lastpage
70
Abstract
This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oilpaper insulation of these transformers were investigated, and results are presented. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper-wrapped insulated conductors in different environments over a temperature range of 115 to 145 ??C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described.
Keywords
Accelerated aging; Conductors; History; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Pulp manufacturing; Temperature measurement; Voltage measurement; Power transformer; condition monitoring; dielectric measurement; insulation aging; insulation life; molecular weight; polarization; transformer insulation;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312523
Filename
4312523
Link To Document