• DocumentCode
    1186621
  • Title

    Experience with Return Voltage Measurements for Assessing Insulation Conditions in Service Aged Transformers

  • Author

    Saha, Tapan Kumar ; Yao, Z. T.

  • Author_Institution
    University of Queensland
  • Volume
    22
  • Issue
    8
  • fYear
    2002
  • Firstpage
    70
  • Lastpage
    70
  • Abstract
    This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oilpaper insulation of these transformers were investigated, and results are presented. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper-wrapped insulated conductors in different environments over a temperature range of 115 to 145 ??C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described.
  • Keywords
    Accelerated aging; Conductors; History; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Pulp manufacturing; Temperature measurement; Voltage measurement; Power transformer; condition monitoring; dielectric measurement; insulation aging; insulation life; molecular weight; polarization; transformer insulation;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2002.4312523
  • Filename
    4312523