The Response of Strain Bus to Short-Circuit Currents
Author :
Craig, D.B. ; Ford, G.L.
Author_Institution :
Ontario Hydro Research Division
Issue :
2
fYear :
1980
fDate :
3/1/1980 12:00:00 AM
Firstpage :
434
Lastpage :
442
Abstract :
Calculation methods for conductor tensions and displacements of strain bus under short-circuit conditions are compared with the results of full scale high current tests. The good agreement between theory and experiment has allowed use of these methods in designing new 100 kA substations and in uprating existing substations from 40 kA to 70 kA.
Keywords :
Capacitive sensors; Circuit faults; Conductors; Fault currents; Hardware; Poles and towers; Structural beams; Substations; Testing; Timing;