Title :
USA-USSR Investigation of 1200-kV Tower Insulation
Author :
Young, F.S. ; Schneider, H.M. ; Gutman, Y.M. ; Tikhodeyev, N.N.
Author_Institution :
Electric Power Research Institute
fDate :
3/1/1980 12:00:00 AM
Abstract :
Results of the joint USA/USSR investigations on 1200-kV tower air Faps and insulator strings are reported for a comprenensive range of times to crest of applied switching impulses extending from about 100 microseconds to 6 milliseconds. Tests were performed in the USA with a conventional impulse generator and in the USSR with cascade transformers. As a result of these investigations, data are available for the first time on similar test objects stressed by two different types of voltage waveforms. A technique for comparing the results based on the concept of the "active part" of the waveshape is described and applied to the data.
Keywords :
Conductors; Financial advantage program; Impulse testing; Laboratories; Performance evaluation; Poles and towers; Power transformer insulation; Power transmission lines; Surges; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1980.319681