• DocumentCode
    1186813
  • Title

    Transmission Line Tower Grounding Performance in Non-Uniform Soil

  • Author

    Dawalibi, F. ; Finney, W.G.

  • Author_Institution
    Montel, Inc.
  • Issue
    2
  • fYear
    1980
  • fDate
    3/1/1980 12:00:00 AM
  • Firstpage
    471
  • Lastpage
    479
  • Abstract
    Detailed computer analyses of a 765 kV typical transmission tower footing grounding performance during phase-to-ground fault condition are described and discussed. It is assumed the tower is erected on a two-layer earth structure. The tower resistance, worst touch and step potentials, are calculated for various soil conditions described by the top layer height and both layer resistivities. Universal charts are presented to help the engineer in predicting and designing transmission tower ground performance.
  • Keywords
    Conductivity; Earth; Fault currents; Grounding; Immune system; Lightning; Poles and towers; Soil; Transmission lines; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1980.319682
  • Filename
    4113825