DocumentCode
1186915
Title
Calculation of Circulating Current Losses in Cable Conductors
Author
Kalsi, SS ; Minnich, SH
Author_Institution
General Electric Company
Issue
2
fYear
1980
fDate
3/1/1980 12:00:00 AM
Firstpage
558
Lastpage
563
Abstract
Conductors for power cable of large cross section are commonly built up from concentrically stranded bundles, which may be compacted to trapezoidal or sector shape. Concentric stranding does not constitute perfect transposition relative to the non-uniform self-field of the cable. While not normally significant at room temperature, the imperfect transposition can lead to large losses in cryogenic cables.
Keywords
Conductivity; Conductors; Cryogenics; Eddy currents; Geometry; Power cables; Samarium; Superconducting cables; Temperature; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1980.319701
Filename
4113837
Link To Document