DocumentCode :
1187023
Title :
Automatic Phase Shift Method for Islanding Detection of Grid-Connected Photovoltaic Inverters
Author :
Hung, Guo-Kiang ; Chang, Chih-Chang ; Chen, Chern-Lin
Author_Institution :
National Taiwan University; AmbitMicrosystems Co.
Volume :
22
Issue :
9
fYear :
2002
Firstpage :
55
Lastpage :
55
Abstract :
The traditional frequency-shift methods for islanding detection of grid connected PV inverters (the active frequency-drift method and the slip mode frequency-shift method) become ineffective under certain paralleled RLC loads. The automatic phase-shift method is proposed in this paper to alleviate this problem. The method is based on the phase shift of the sinusoidal inverter output current. When the utility malfunctions, the phase-shift algorithm keeps the frequency of the inverter terminal voltage deviating until the protection circuit is triggered. Simulation and experiments are performed for verification.
Keywords :
Coaxial cables; Dielectrics; Frequency; Fuzzy logic; Inverters; Load forecasting; Phase detection; Photovoltaic systems; Pyroelectricity; Solar power generation; Automatic phase shift; grid-connected photovoltaic inverters; inverters; islanding detection;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2002.4312568
Filename :
4312568
Link To Document :
بازگشت