DocumentCode
1187428
Title
Experimental Facility for Investigation of Lightning Performance of Distribution Lines
Author
Nakada, Kazuo ; Sugimoto, Hitoshi ; Yokoyama, Shigeru
Author_Institution
Hokuriku Electric Power Co.; CRIEPI
Volume
22
Issue
9
fYear
2002
Firstpage
63
Lastpage
63
Abstract
In order to clarify the lightning performance of a distribution line, test distribution lines and a test tower were constructed at the Mikuni Testing Center of Hokuriku Electric Power Co. in 1999. Using these facilities, we observed transient voltages and current distributions due to direct strokes of natural lightning. Based on this data, we have clarified the following points: calculated voltages and currents using the EMTP agree with the experimental results fairly well; for lightning currents of long durations, however, the reduction of voltages across arresters by energy absorption should be taken into consideration.
Keywords
Damping; EMTP; Frequency; Lightning; Power capacitors; Power system harmonics; Resonance; Testing; Thyristors; Voltage; EMTP; Natural lightning; direct stroke; distribution line; surge arrester;
fLanguage
English
Journal_Title
Power Engineering Review, IEEE
Publisher
ieee
ISSN
0272-1724
Type
jour
DOI
10.1109/MPER.2002.4312611
Filename
4312611