DocumentCode :
1188779
Title :
Investigation of Interrupting Performance of Puffer Type Gas Blast Circuit Breaker Under Various Nozzle Clogging Conditions
Author :
Yoshioka, Yoshio ; Nakagawa, Yukio
Author_Institution :
Hitachi Research Laboratory, Hitachi Ltd.
Issue :
6
fYear :
1980
Firstpage :
2086
Lastpage :
2093
Abstract :
The interrupting ability of a puffer type Gas Blast Circuit Breaker (GCB) was investigated under various nozzle clogging conditions. A model puffer type GCB was used in the interrupting experiments, in which nozzle diameter, nozzle geometry and current wave form were varied. The following results were obtained from the experiments, 1 At a nozzle current density of 2.5-5.5kA/cm2, the low puffer pressure makes it possible to interrupt a current with a large dI/dt. 2 An increase of base gas pressure effectively contributes to improving interrupting ability. 3 The puffer chamber pressure rise which is caused by excess nozzle clogging does not improve interrupting ability.
Keywords :
Circuit breakers; Current density; Engine cylinders; Europe; Geometry; Interrupters; Laboratories; Pistons; Reservoirs; Solid modeling;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1980.319850
Filename :
4114045
Link To Document :
بازگشت