Title :
Application of Synthetic Auto-Reclosing Circuit for Testing High-Voltage Circuit-Breakers
Author :
Manganaro, S. ; Schramm, H.H.
Author_Institution :
CESI
Abstract :
A synthetic test circuit has been developed to test high-voltage circuit-breakers with respect to their making and auto-reclosing performance at full voltage and full current. The validity of making tests performed at full parameters or at reduced voltahage is checked. The test circuit is applied upon a 420 kV SF6 puffer type circuit-breaker with two breaks per phase. Testing this circuit-breaker can be considered of special interest; particular attention has to be paid to its pre-arcing conditions as due to its high no minal voltage per break.
Keywords :
Circuit faults; Circuit stability; Circuit testing; Interrupters; Laboratories; Performance evaluation; Power generation economics; Sulfur hexafluoride; System testing; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1980.319852