Development of 500-kV XLPE cables and accessories for long distance underground transmission line-Part I: insulation design of cables
Author
Kubota, Takeo ; Takahashi, Yoshihisa ; Sakuma, Susumu ; Watanabe, Masaru ; Kanaoka, Mamoru ; Yamanouchi, Hiroshi
Author_Institution
Tokyo Electr. Power Co. Inc., Japan
Volume
9
Issue
4
fYear
1994
fDate
10/1/1994 12:00:00 AM
Firstpage
1741
Lastpage
1749
Abstract
This paper discusses the results of a basic study for the development of 500 kV XLPE power cables. The authors have established that the factors that decide the performance of today´s XLPE cables are impurities in the insulator and protrusions on the semiconductive layer, and that the insulation performance of XLPE power cables is determined by the size of these defects. In model tests of XLPE power cables, the minimum insulation breakdown stress of cables was determined, to set the design values for 500 kV XLPE cable. As a result, it was found that it is possible to design cables having an insulation thickness of 25 mm
Keywords
XLPE insulation; design engineering; electric breakdown; insulation testing; power cable testing; power transmission lines; underground cables; 25 mm; 500 kV; EHV; XLPE power cables; breakdown stress; defects; development; insulation design; long distance underground transmission line; model tests; performance; semiconductive layer; thickness; Cable insulation; Dielectrics and electrical insulation; Electric breakdown; Oil filled cables; Power cables; Power transmission; Power transmission lines; Stress; Underground power cables; Urban areas;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.329507
Filename
329507