• DocumentCode
    1189612
  • Title

    Principal decomposition by-products generated at various abnormalities in gas-insulated transformers

  • Author

    Nukaiyama, Y. ; Takagi, I. ; Ishihara, H. ; Kudo, A. ; Maki, Y. ; Hosokawa, N.

  • Author_Institution
    Chubu Electric Power Co. Inc., Nagoya, Japan
  • Volume
    9
  • Issue
    4
  • fYear
    1994
  • fDate
    10/1/1994 12:00:00 AM
  • Firstpage
    1885
  • Lastpage
    1891
  • Abstract
    Gas analysis provides a promising means for a diagnosis of gas-insulated equipment. Although many studies have been concentrated on SF6 gas decomposition, they were mostly related to the faults in GIS systems and not directly applicable to gas-insulated transformers, which have much more complicated material structure. An experimental survey on decomposition by-products at various abnormal conditions was carried out by use of simulation models to develop a diagnostic method for gas-insulated transformers based on gas and ion chromatograph analyses. Major components characteristic in each abnormality, such as SO2 on metal overheat, SO2F 2 on partial discharges, etc. were identified by the experiments
  • Keywords
    SF6 insulation; chromatography; decomposition; gas insulated transformers; insulation testing; power transformer insulation; power transformer testing; SF6; SO2; SO2F2; decomposition by-products; diagnostic method; gas analysis; gas chromatograph analyses; gas-insulated transformers; ion chromatograph analyses; metal overheat; partial discharges; simulation models; Analytical models; Geographic Information Systems; Partial discharges; Power system reliability; Power transformer insulation; Predictive maintenance; Pressing; Substations; Sulfur hexafluoride; Urban areas;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.329521
  • Filename
    329521