DocumentCode :
1193453
Title :
Application of Two-Phase Spray Cooling for Thermal Management of Electronic Devices
Author :
Visaria, Milan ; Mudawar, Issam
Author_Institution :
Boiling & Two-Phase Flow Lab. (BTPFL), Purdue Univ., West Lafayette, IN, USA
Volume :
32
Issue :
4
fYear :
2009
Firstpage :
784
Lastpage :
793
Abstract :
Recent studies provide ample evidence of the effectiveness of two-phase spray cooling at dissipating large heat fluxes from electronic devices. However, those same studies point to the difficulty predicting spray performance, given the large number of parameters that influence spray behavior. This paper provides a complete set of models/correlations that are required for designing an optimum spray cooling system. Several coolants (water, FC-72, FC-77, FC-87 and PF-5052) are used to generate a comprehensive spray-cooling database for different nozzles, flow rates, subcoolings, and orientations. High-speed video motion analysis is used to enhance the understanding of droplet formation and impact on the device´s surface, especially near the critical heat flux (CHF) point. A previous CHF correlation for normal sprays is modified for both inclination and subcooling effects. A new user-friendly CHF correlation is recommended which shows excellent predictive capability for the entire database. Also discussed in this paper is a new theoretical scheme for assessing the influence of spray overlap on cooling performance.
Keywords :
cooling; thermal management (packaging); CHF correlation; critical heat flux point; electronic devices; flow rates; high-speed video motion analysis; nozzles; optimum spray cooling system; thermal management; two-phase spray cooling; Defense electronics; phase change cooling; spray cooling;
fLanguage :
English
Journal_Title :
Components and Packaging Technologies, IEEE Transactions on
Publisher :
ieee
ISSN :
1521-3331
Type :
jour
DOI :
10.1109/TCAPT.2008.2010405
Filename :
4801563
Link To Document :