DocumentCode :
1194229
Title :
Adaptive load shedding for isolated power systems
Author :
Thompson, J.G. ; Fox, B.
Author_Institution :
Dept. of Electr. & Electron. Eng., Queen´´s Univ., Belfast, UK
Volume :
141
Issue :
5
fYear :
1994
fDate :
9/1/1994 12:00:00 AM
Firstpage :
491
Lastpage :
496
Abstract :
Emergency control of frequency in an isolated power system is considered. In many such systems, limited load shedding is permitted under certain generation loss conditions to reduce the expense of spinning reserve provision. It is important in these circumstances to minimise consumer disruption through proper-design of the load shedding arrangements. An adaptive load shedding scheme is proposed, based on intelligent relays supplied with updated values of key system parameters in addition to the usual measurement of frequency. Results are presented to demonstrate the ability of the proposed scheme to reduce potential load shedding to a value close to the theoretical minimum
Keywords :
adaptive control; frequency control; frequency measurement; load shedding; power system control; power system measurement; relay protection; adaptive load shedding; frequency control; frequency measurement; generation loss conditions; intelligent relays; isolated power systems; limited load shedding; spinning reserve provision;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:19941370