DocumentCode :
1195946
Title :
A Self-Isolation Method for the HIF Zone Under the Network-Based Distribution System
Author :
Ko, Yun-Seok
Author_Institution :
Dept. of Electron. Eng., Namseoul Univ., Chungnam
Volume :
24
Issue :
2
fYear :
2009
fDate :
4/1/2009 12:00:00 AM
Firstpage :
884
Lastpage :
891
Abstract :
When a high-impedance fault (HIF) occurs in any zone of a distribution system, it is very difficult to detect the fault because the fault current is very small and the time of its occurrence cannot be ascertained. This paper proposes a self-isolation method for an HIF zone in which the feeder remote terminal unit (FRTU) experiencing nil-voltage can identify and isolate autonomously an HIF zone by exchanging voltage and current information with the neighbor FRTUs on the feeder when an HIF occurs under the network-based distribution system. Also, the method was devised to enhance the reliability of HIF identification from the voltage sensor error. Furthermore, new and simple heuristics are proposed, which are required to classify the nil-voltage due to an HIF with nil-voltage caused by general fault outage, scheduled outage, and outage due to the reclosing operation of a protective device (circuit breaker or recloser).
Keywords :
fault currents; power distribution faults; fault current; feeder remote terminal unit; high-impedance fault zone; network-based distribution system; self-isolation method; voltage sensor error; Distribution automation system (DAS); distribution system; feeder remote terminal unit (FRTU); high impedance fault (HIF); network-based system; self-identification; self-isolation;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2014482
Filename :
4802017
Link To Document :
بازگشت