DocumentCode :
1196301
Title :
Estimation of β for adaptive frequency bias setting in load frequency control
Author :
Chang-Chien, Le-Ren ; Hoonchareon, Naeb-Boon ; Ong, Chee-Mun ; Kramer, Robert A.
Author_Institution :
Sch. of Electr. & Comput. Eng., Purdue Univ., West Lafayette, IN, USA
Volume :
18
Issue :
2
fYear :
2003
fDate :
5/1/2003 12:00:00 AM
Firstpage :
904
Lastpage :
911
Abstract :
Utilities in the US use tie-line bias control to share generation and frequency support in the interconnection. To ensure that the reliability and the responsibility of frequency support are maintained, NERC guidelines specify that the frequency bias coefficient -10 B that a control area uses in its tie-line control be set as close as practical to the area´s frequency response characteristic β. This paper presents an algorithm to estimate β online using variables commonly available from existing AGC system. Results showing the algorithm´s performance in simulated conditions and on actual field data are presented. Issues related to using the estimated β in an adaptive frequency bias-setting control are examined.
Keywords :
adaptive control; frequency control; frequency response; load regulation; power system control; power system interconnection; NERC guidelines; adaptive frequency bias-setting; automatic generation control; frequency response characteristic; frequency support; load frequency control; reliability; tie-line bias control; Adaptive control; Automatic generation control; Error correction; Frequency control; Frequency estimation; Frequency response; Guidelines; Maintenance; Power engineering and energy; Programmable control;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2003.810996
Filename :