DocumentCode
1196510
Title
Influence of normalization in dynamic reactive load models
Author
Navarro, Inés Romero ; Samuelsson, Olof ; Lindahl, Sture
Author_Institution
Ind. Electr. Eng. & Autom., Lund Univ., Sweden
Volume
18
Issue
2
fYear
2003
fDate
5/1/2003 12:00:00 AM
Firstpage
972
Lastpage
973
Abstract
As an extension of previous studies on modeling and identification of nonlinear dynamic load models, this letter describes the influence of the normalization in dynamic reactive load models. Using measured data from normal operation, it is shown that the reactive power level, which has previously used as normalization factor is inappropriate. If instead apparent power level is used, the variability in the parameters that describe the reactive load response is drastically reduced.
Keywords
load (electric); power system parameter estimation; reactive power; apparent power level; dynamic reactive load models; measured data; nonlinear dynamic load models identification; normal operation; normalization; reactive load response; reactive power level; Equations; Load modeling; Power measurement; Power system dynamics; Power system modeling; Power system transients; Reactive power; Stability analysis; Steady-state; Voltage;