• DocumentCode
    1197675
  • Title

    Dynamic Fault Testing of Ground Sensing Relays

  • Author

    Krick, John B. ; Potts, Charles D.

  • Author_Institution
    Val-Tech, Inc., Delaware Industrial Park
  • Issue
    6
  • fYear
    1983
  • Firstpage
    975
  • Lastpage
    979
  • Abstract
    Performance testing of a ground fault protection system has traditionally been accomplished by simulating high level fault magnitudes at current transformer secondary. For a new chemical manufacturing facility, a procedure was devised to safely stage ground faults on the 480-V distribution system. To implement the procedure, a test set was developed that placed a controlled ground fault on the system and measured current magnitude and tripping time. Tests were conducted without the need to modify the distribution system or the ground protection wiring in any way. This feature revealed discrepancies that would not have been discovered following more conventional test methods.
  • Keywords
    Chemicals; Control systems; Current measurement; Current transformers; Production facilities; Protection; Protective relaying; Relays; System testing; Time measurement;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1983.4504323
  • Filename
    4504323