DocumentCode
1197675
Title
Dynamic Fault Testing of Ground Sensing Relays
Author
Krick, John B. ; Potts, Charles D.
Author_Institution
Val-Tech, Inc., Delaware Industrial Park
Issue
6
fYear
1983
Firstpage
975
Lastpage
979
Abstract
Performance testing of a ground fault protection system has traditionally been accomplished by simulating high level fault magnitudes at current transformer secondary. For a new chemical manufacturing facility, a procedure was devised to safely stage ground faults on the 480-V distribution system. To implement the procedure, a test set was developed that placed a controlled ground fault on the system and measured current magnitude and tripping time. Tests were conducted without the need to modify the distribution system or the ground protection wiring in any way. This feature revealed discrepancies that would not have been discovered following more conventional test methods.
Keywords
Chemicals; Control systems; Current measurement; Current transformers; Production facilities; Protection; Protective relaying; Relays; System testing; Time measurement;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1983.4504323
Filename
4504323