DocumentCode
1198467
Title
The Impact of Sine-Wave Distortions on Protective Relays
Author
Power System Relaying Committee
Issue
2
fYear
1984
fDate
3/1/1984 12:00:00 AM
Firstpage
335
Lastpage
343
Abstract
Sine wave distortions on power systems are shown to affect the performance of both electromechanical protective relays of classical designs and static relays of various designs. Digital based (computer) relay systems do not circumvent, per se, wave distortion problems. Protection relays are shown to not respond to any single parameter such as the rms value or the fundamental component, of an applied signal. It is noted that there are no wave distortion performance standards nor waveform testing standards for protective relays, other than for harmonic restraint relays. This can be attributed to the lack of recognizing as a significant factor the causal relationship between relay performance and waveform distortion. This is an interim report constituting about 20 percent of a contemplated special report, "Sine Wave Distortions on Power Systems and the Impact on, Protective Relaying". A bibliography on the larger subject is included.
Keywords
Bibliographies; Digital relays; Harmonic distortion; Manufacturing; Power system harmonics; Power system interconnection; Power system protection; Power system relaying; Protective relaying; Testing;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.1984.4504416
Filename
4504416
Link To Document