• DocumentCode
    1199318
  • Title

    Determination of Current Transformer Errors at Primary Currents up to 100 000 A

  • Author

    Braun, Andreas

  • Volume
    26
  • Issue
    3
  • fYear
    1977
  • Firstpage
    263
  • Lastpage
    267
  • Abstract
    A method is described for testing precision current transformers, particularly devices with very high values of rated primary current and rated secondary currents up to 200 A. It makes use of the well-known differential method (Arnold, Hohle), substituting, however, the common resistor with an electronic operational amplifier, thus yielding an almost negligible resistance and a very high sensitivity of 0.01 ppm. Results of ratio error measurements are reported at values of primary currents between 500 and 100 000 A.
  • Keywords
    Current measurement; Current transformers; Differential amplifiers; Electric resistance; Electrical resistance measurement; Electronic equipment testing; Energy measurement; Operational amplifiers; Power generation; Resistors;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.1977.4314550
  • Filename