DocumentCode
1200130
Title
Stresses on Grounding Switches During Opening
Author
Habedank, U. ; Luehrmann, H.M.
Author_Institution
SIEMENS AG
Issue
5
fYear
1985
fDate
5/1/1985 12:00:00 AM
Firstpage
1225
Lastpage
1232
Abstract
The stresses upon grounding switches under the following conditions are examined: out of two parallel AC lines, one is carrying its rated current and the other is isolated and grounded at both ends by means of grounding switches. Under these conditions, the grounding switches must carry the induced steady-state current. When grounding is cancelled, they must interrupt the induced current and withstand the transient recovery voltage (TRV). The value of the current and the TRV depend upon the sequence of opening of the grounding switches.
Keywords
Circuit testing; Equations; Grounding; Steady-state; Stress; Switches; Switchgear; System testing; Transient analysis; Voltage;