Title :
Estimation of the surge arrester outage rate caused by lightning overvoltages
Author_Institution :
Fac. of Electr. Eng., Univ. of Belgrade, Serbia
Abstract :
The computation based on the lightning limiting parameters method of the surge arrester minimum energy absorption capability is presented. The sensitivity analyses of certain lightning parameters like lightning current-wave duration and equivalent circuit parameters are performed. The influence of the tower footing impedance to the surge arrester failure rate due to the exceeding energy absorption capability is investigated. The method of selection of the medium voltage surge arrester energy absorption capability based on the allowed failure rate is proposed.
Keywords :
arresters; equivalent circuits; lightning protection; overvoltage; sensitivity analysis; energy absorption capability; equivalent circuit parameter; lightning current wave duration; lightning discharge; lightning overvoltages; parameter method limitation; sensitivity analysis; surge arrester failure; surge arrester outage rate; tower footing impedance; voltage surge arrester energy absorption; Absorption; Arresters; Equivalent circuits; Lightning; Manufacturing; Medium voltage; Poles and towers; Sensitivity analysis; Surge protection; Testing; Lightning discharges; medium voltage networks; surge arresters;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2004.835435