• DocumentCode
    1200323
  • Title

    Dynamic thermal modelling of power transformers

  • Author

    Susa, Dejan ; Lehtonen, Matti ; Nordman, Hasse

  • Author_Institution
    Power Syst. Lab., Helsinki Univ. of Technol., Espoo, Finland
  • Volume
    20
  • Issue
    1
  • fYear
    2005
  • Firstpage
    197
  • Lastpage
    204
  • Abstract
    The aim of this paper is to introduce hot-spot and top-oil temperature thermal models for more accurate temperature calculations during transient states based on data received in a normal heat run test (i.e., the top oil in the tank of the transformer and the average winding-to-average oil gradient). Oil viscosity changes and loss variation with temperature are taken into account. The new thermal models will be validated using experimental (fiber-optic test) results obtained at varying load current on a 250-MVA-ONAF-cooled unit, a 400-MVA-ONAF-cooled unit and a 605-MVA-OFAF-cooled unit. The results are also compared with the IEEE-Loading guide (1995) Annex G method.
  • Keywords
    power transformers; temperature; transformer oil; viscosity; 250 MVA; 400 MVA; 605 MVA; Annex G method; IEEE loading guide; dynamic thermal modelling; fiber optic test; hot spot temperature; oil viscosity; power transformer; top-oil temperature thermal model; varying load current; Capacitance; Cooling; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Temperature; Testing; Thermal resistance; Viscosity; Hot-spot temperature; power transformer; top-oil temperature;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2004.835255
  • Filename
    1375095