• DocumentCode
    1201416
  • Title

    Siniglee-Staagee Amnplifierr-Aideed Current Transformers Possessing Small Ratio Errors at 60 Hz

  • Author

    Beard, Geoffrey E.

  • Volume
    28
  • Issue
    2
  • fYear
    1979
  • fDate
    6/1/1979 12:00:00 AM
  • Firstpage
    141
  • Lastpage
    146
  • Abstract
    Two directly coupled electronic techniques are described which reduce significantly the burden seen by a single-stage toroidal current transformer. Almost all the power is supplied by an electronic power amplifier so that magnetizing current within the transformer is extremely small Magnetic cores of small physical size may be used with small numbers of turns. Measured ratio errors at unity ratio are approximately 10 parts per million or less at 60 Hz provided certain restrictions are satisfied with respect to dc offset voltages within the electronic amplifier used. This particular technique lends itself to the use of modern packaged linear amplifiers which may be adapted for power use. Directly coupled electronic circuitry enables the techniques to be used at lower frequencies. Ratio error measurements are described and comparison made between the actual ratio errors obtained experimentally and the theoretically predicted values.
  • Keywords
    Capacitance; Current transformers; Frequency; Impedance; Magnetic cores; Magnetic flux; Power amplifiers; Power supplies; Toroidal magnetic fields; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.1979.4314782
  • Filename
    4314782