• DocumentCode
    1202672
  • Title

    Voltage-Distortion Compensation in Electrical Plants Supplying Static Power Converters

  • Author

    Montanari, Gian Carlo ; Loggini, Mauro

  • Author_Institution
    Faculty of Engineering, University of Bologna, Institute of Industrial Electrical Engineering, Viale Risorgimento 2, 40136 Bologna, Italy.
  • Issue
    1
  • fYear
    1987
  • Firstpage
    181
  • Lastpage
    188
  • Abstract
    Voltage distortion compensation is a problem that must often be tackled in electrical plants supplying nonlinear loads, such as static power converters, both to ensure reliable behavior of apparatus sensible to harmonics and to comply with standard limits. Analysis of the compensation system constituted by harmonic filters and protection reactance is carried out, to clarify their contribution to voltage distortion factor improvement and fundamental project criteria. To this end a study of the current commutation transient, cause of voltage notches and, hence, of voltage distortion, is performed in the presence of filters, and the distortion factor is calculated by means of two separate methods. Comparison between these methods, based on voltage notches and harmonic voltage drop, respectively, and determination of the expressions for estimating the overlap angle after filter insertion allow the influence of filters on the line and the converter to be analyzed.
  • Keywords
    Harmonic analysis; Harmonic distortion; Harmonic filters; Power harmonic filters; Power supplies; Power system harmonics; Power system protection; Power system reliability; Static power converters; Voltage;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.1987.4504884
  • Filename
    4504884