• DocumentCode
    1204608
  • Title

    An Automated Noncontact Measurement System for Current Harmonics in Aerial Transmission and Distribution Systems

  • Author

    Cyganski, David ; Orr, John A. ; Emanuel, Alexander Eigeles ; Gulachenski, Edward M. ; Pileggi, David J.

  • Volume
    33
  • Issue
    1
  • fYear
    1984
  • fDate
    3/1/1984 12:00:00 AM
  • Firstpage
    31
  • Lastpage
    36
  • Abstract
    Using magnetic field data from under aerial power transmission lines, tomographic reconstruction techniques have been applied to determine the magnitudes and phases of currents in each power conductor. Phasor current values at fundamental (60 Hz) and harmonic frequencies are produced. This measurement technique requires no physical contact with power lines (even by clamp-around transformers) and hence should be convenient for monitoring and trouble-shooting cases of excessive harmonic currents on transmission and distribution facilities. The method has been implemented experimentally, and laboratory and initial field tests have demonstrated its basic validity.
  • Keywords
    Conductors; Current measurement; Frequency; Magnetic field measurement; Measurement techniques; Monitoring; Power transmission lines; Tomography; Transformers; Transmission line measurements;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.1984.4315147
  • Filename
    4315147