DocumentCode
1204608
Title
An Automated Noncontact Measurement System for Current Harmonics in Aerial Transmission and Distribution Systems
Author
Cyganski, David ; Orr, John A. ; Emanuel, Alexander Eigeles ; Gulachenski, Edward M. ; Pileggi, David J.
Volume
33
Issue
1
fYear
1984
fDate
3/1/1984 12:00:00 AM
Firstpage
31
Lastpage
36
Abstract
Using magnetic field data from under aerial power transmission lines, tomographic reconstruction techniques have been applied to determine the magnitudes and phases of currents in each power conductor. Phasor current values at fundamental (60 Hz) and harmonic frequencies are produced. This measurement technique requires no physical contact with power lines (even by clamp-around transformers) and hence should be convenient for monitoring and trouble-shooting cases of excessive harmonic currents on transmission and distribution facilities. The method has been implemented experimentally, and laboratory and initial field tests have demonstrated its basic validity.
Keywords
Conductors; Current measurement; Frequency; Magnetic field measurement; Measurement techniques; Monitoring; Power transmission lines; Tomography; Transformers; Transmission line measurements;
fLanguage
English
Journal_Title
Instrumentation and Measurement, IEEE Transactions on
Publisher
ieee
ISSN
0018-9456
Type
jour
DOI
10.1109/TIM.1984.4315147
Filename
4315147