DocumentCode
1210244
Title
On the resonance effects due to ground wires in transmission lines with non-uniform soil conductivity and non-uniform tower resistances
Author
Faria, J. A Brandgo
Author_Institution
Dept. of Electr. Eng., Univ. Tecnica de Lisboa, Portugal
Volume
7
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
29
Lastpage
38
Abstract
High-frequency resonance effects due to shield wire grounding may affect carrier transmission performance in the vicinity of certain critical frequencies. The authors investigate whether nonuniformities in soil conductivity and in tower footing resistances along the power line may lead to the suppression of such resonance effects. Simulation results show that fluctuations in soil conductivity and in lower footing resistance along the line do not by themselves destroy resonance effects
Keywords
earthing; overhead line mechanical characteristics; poles and towers; power overhead lines; resonance; transmission networks; HF; ground wires; mechanical characteristics; power overhead lines; resonance; shield wire grounding; soil conductivity; tower footing resistances; transmission lines; Conductivity; Fluctuations; Frequency; Grounding; Poles and towers; Power transmission lines; Resonance; Soil; Transmission lines; Wires;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.108886
Filename
108886