• DocumentCode
    1211030
  • Title

    Microprocessor based three step quadrilateral distance relay for the protection of EHV/UHV transmission lines

  • Author

    Gangadharan, G. ; Anbalagan, P.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., PSG Coll. of Technol., Coimbatore, India
  • Volume
    7
  • Issue
    1
  • fYear
    1992
  • fDate
    1/1/1992 12:00:00 AM
  • Firstpage
    91
  • Lastpage
    97
  • Abstract
    The development of a three-zone quadrilateral distance relay for the protection of EHV/UHV transmission lines is discussed. The proposed scheme is based on the Fourier transform method of extracting the fundamental components of voltage and current signals from nonsinusoidal post fault signals. The determination of the quadrilateral characteristic is completed through software. The relay is successfully tested for a number of different three-step quadrilateral characteristics. It is shown that any quadrilateral characteristic can be obtained. Recommendations are made on using 16 bit microprocessors to reduce the operating time and for better accuracy
  • Keywords
    Fourier transforms; microcomputer applications; power system computer control; power system protection; power transmission lines; relay protection; 16 bit microprocessors; EHV; Fourier transform; UHV; current; development; digital control; nonsinusoidal post fault signals; power system protection; software; three step quadrilateral distance relay; transmission lines; voltage; Circuit faults; Fourier transforms; Frequency; Microprocessors; Power system protection; Power transmission lines; Protective relaying; Testing; Voltage; Voltage-controlled oscillators;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.108894
  • Filename
    108894