DocumentCode
1211030
Title
Microprocessor based three step quadrilateral distance relay for the protection of EHV/UHV transmission lines
Author
Gangadharan, G. ; Anbalagan, P.
Author_Institution
Dept. of Electr. & Electron. Eng., PSG Coll. of Technol., Coimbatore, India
Volume
7
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
91
Lastpage
97
Abstract
The development of a three-zone quadrilateral distance relay for the protection of EHV/UHV transmission lines is discussed. The proposed scheme is based on the Fourier transform method of extracting the fundamental components of voltage and current signals from nonsinusoidal post fault signals. The determination of the quadrilateral characteristic is completed through software. The relay is successfully tested for a number of different three-step quadrilateral characteristics. It is shown that any quadrilateral characteristic can be obtained. Recommendations are made on using 16 bit microprocessors to reduce the operating time and for better accuracy
Keywords
Fourier transforms; microcomputer applications; power system computer control; power system protection; power transmission lines; relay protection; 16 bit microprocessors; EHV; Fourier transform; UHV; current; development; digital control; nonsinusoidal post fault signals; power system protection; software; three step quadrilateral distance relay; transmission lines; voltage; Circuit faults; Fourier transforms; Frequency; Microprocessors; Power system protection; Power transmission lines; Protective relaying; Testing; Voltage; Voltage-controlled oscillators;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.108894
Filename
108894