• DocumentCode
    1211227
  • Title

    Design, implementation and testing of a microprocessor-based high-speed relay for detecting transformer winding faults

  • Author

    Sidhu, T.S. ; Sachdev, M.S. ; Wood, H.C. ; Nagpal, M.

  • Author_Institution
    Power Syst. Res. Group Saskatchewan Univ., Saskatoon, Sask., Canada
  • Volume
    7
  • Issue
    1
  • fYear
    1992
  • fDate
    1/1/1992 12:00:00 AM
  • Firstpage
    108
  • Lastpage
    117
  • Abstract
    The authors present the design, implementation and testing of a microprocessor-based high-speed relay that correctly detects transformer winding faults. Instead of relying on the presence of harmonics to identify magnetizing inrush, it uses a nonlinear model of the transformer to determine the state of its health. One version of the relay is suitable for protecting single-phase transformers, whereas another version is for protecting three-phase transformers. A three-phase delta-wye 15 kVA transformer was used to test the relay for a variety of operating conditions. The results show that the relay performs well
  • Keywords
    fault location; microcomputer applications; power system computer control; power system protection; power transformers; relay protection; transformer protection; transformer windings; 15 kVA; delta-wye; design; fault location; high-speed relay; microprocessors; nonlinear model; power system protection; power transformers; single-phase; testing; three-phase; transformer winding; Digital relays; Electrical fault detection; Hardware; Power system harmonics; Power system protection; Power system relaying; Power transformers; Protective relaying; Testing; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.108896
  • Filename
    108896