• DocumentCode
    1211509
  • Title

    Development of fault characterization equipment (FCAREC) for power transmission lines

  • Author

    Tsuji, Koulchl ; Yanagida, Hlkonl ; Sasaki, Hlroshl ; Abe, Shigeru

  • Author_Institution
    Hokuriku Electr. Power Co., Toyama, Japan
  • Volume
    7
  • Issue
    1
  • fYear
    1992
  • fDate
    1/1/1992 12:00:00 AM
  • Firstpage
    133
  • Lastpage
    138
  • Abstract
    The authors present fault characterization equipment (FCAREC) which detects fault resistances in a time sequence, in addition to the conventional determination of fault location. The objective of FCAREC is to offer improved functions to estimate causes of system faults. The equipment works by solving a circuit equation, using voltage and current data and line constants at each end of a particular line. To reduce the effects of data measurement errors, a high-precision calculation based on the least squares method is used. Since December 1989, the prototype FCAREC equipment has been used in feasibility tests on 154 kV parallel double transmission lines. During the tests, three power system faults were experienced and satisfactory results were obtained in all cases
  • Keywords
    fault location; least squares approximations; power systems; power transmission lines; 154 kV; FCAREC; circuit equation; current; fault characterization equipment; fault location; fault resistances; least squares method; line constants; power system; power transmission lines; time sequence; voltage; Circuit faults; Circuit testing; Electrical fault detection; Equations; Fault detection; Fault location; Least squares methods; Measurement errors; Prototypes; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.108899
  • Filename
    108899