DocumentCode
1211509
Title
Development of fault characterization equipment (FCAREC) for power transmission lines
Author
Tsuji, Koulchl ; Yanagida, Hlkonl ; Sasaki, Hlroshl ; Abe, Shigeru
Author_Institution
Hokuriku Electr. Power Co., Toyama, Japan
Volume
7
Issue
1
fYear
1992
fDate
1/1/1992 12:00:00 AM
Firstpage
133
Lastpage
138
Abstract
The authors present fault characterization equipment (FCAREC) which detects fault resistances in a time sequence, in addition to the conventional determination of fault location. The objective of FCAREC is to offer improved functions to estimate causes of system faults. The equipment works by solving a circuit equation, using voltage and current data and line constants at each end of a particular line. To reduce the effects of data measurement errors, a high-precision calculation based on the least squares method is used. Since December 1989, the prototype FCAREC equipment has been used in feasibility tests on 154 kV parallel double transmission lines. During the tests, three power system faults were experienced and satisfactory results were obtained in all cases
Keywords
fault location; least squares approximations; power systems; power transmission lines; 154 kV; FCAREC; circuit equation; current; fault characterization equipment; fault location; fault resistances; least squares method; line constants; power system; power transmission lines; time sequence; voltage; Circuit faults; Circuit testing; Electrical fault detection; Equations; Fault detection; Fault location; Least squares methods; Measurement errors; Prototypes; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.108899
Filename
108899
Link To Document