Abstract :
Chemical and thermal degradation of electrical insulation in oil-filled transformers, mechanisms of failure and methods of condition monitoring and of life prediction are reviewed. An insulation life prediction model is developed and estimates of insulation life are presented under a variety of oil/paper conditions. Systematic measurements of the concentration of chemical indicators in transformer oil are used to demonstrate that furaldehyde and related products can be used to detect high rates of paper degradation. Similarly, phenol and related products indicate electrical degradation in phenol-formaldehyde resins
Keywords :
fault location; indicators; insulating oils; insulation testing; paper; power transformers; transformer insulation; cellulosic electrical paper insulation; chemical degradation; chemical indicators; condition monitoring; degradation; electrical degradation; electrical insulation; failure; furaldehyde; insulation life prediction model; life prediction; oil-filled transformers; paper degradation; phenol; phenol-formaldehyde resins; power transformers; thermal degradation;
fLanguage :
English
Journal_Title :
Science, Measurement and Technology, IEE Proceedings -
Publisher :
iet
ISSN :
1350-2344
Type :
jour
DOI :
10.1049/ip-smt:19949957
Filename :
338827
Link To Document :
بازگشت