• DocumentCode
    1212550
  • Title

    No-load loss measurements of power transformers under distorted supply voltage waveform conditions

  • Author

    So, Eddy ; Arseneau, Rejean ; Hanique, Ernst

  • Author_Institution
    Nat. Res. Council of Canada, Ottawa, Ont., Canada
  • Volume
    52
  • Issue
    2
  • fYear
    2003
  • fDate
    4/1/2003 12:00:00 AM
  • Firstpage
    429
  • Lastpage
    432
  • Abstract
    This paper describes the problem of correcting the results of no-load loss measurements of power transformers for the effect of distorted supply voltage waveform on the magnetic flux in the core and hence on both the hysteresis and eddy current loss components of core losses. Test data obtained during the no-load loss measurements of a three phase 675-MVA power transformer was reproduced at the National Research Council of Canada laboratory to demonstrate the instrumentation requirements to ensure a proper application of the correction formula.
  • Keywords
    eddy currents; loss measurement; magnetic flux; magnetic hysteresis; power transformer testing; 675 MVA; National Research Council of Canada; core losses; distorted supply voltage waveform conditions; eddy current loss components; hysteresis; instrumentation requirements; magnetic flux; no-load loss measurements; power transformers; Current measurement; Distortion measurement; Eddy currents; Loss measurement; Magnetic cores; Magnetic flux; Magnetic hysteresis; Power measurement; Power transformers; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Instrumentation and Measurement, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9456
  • Type

    jour

  • DOI
    10.1109/TIM.2003.809910
  • Filename
    1202066