DocumentCode :
1212916
Title :
Fast method to determine an area of vulnerability for stochastic prediction of voltage sags
Author :
Park, C.-H. ; Jang, G.
Author_Institution :
Dept. of Electr. Eng., Korea Univ., Seoul, South Korea
Volume :
152
Issue :
6
fYear :
2005
Firstpage :
819
Lastpage :
827
Abstract :
A fast method determines the areas of vulnerability for sensitive loads in a mesh network. The area of vulnerability for a sensitive load is essential for the estimation of the expected number of voltage sags from the utility system. In general, an area of vulnerability is determined by performing a short-circuit analysis at many different points on lines and buses. Such a method is inefficient for identifying the area of vulnerability in a large mesh network. Two equations of the voltage-sag magnitudes and phase-angle jumps due to faults along a line are derived by using the impedance matrix building algorithm. By using the derived equation of voltage-sag magnitude, the area of vulnerability can be determined without performing short-circuit analysis. A fast and efficient numerical method to identify the area of vulnerability is also described. The method developed was used to determine the areas of vulnerability for three sensitive loads in the IEEE 30-bus test system.
Keywords :
impedance matrix; power supply quality; power system faults; power system reliability; short-circuit currents; stochastic processes; IEEE 30-bus test system; impedance matrix building algorithm; line faults; mesh network; phase-angle jumps; sensitive loads; short-circuit analysis; stochastic prediction vulnerability; voltage-sag magnitudes;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20050082
Filename :
1532100
Link To Document :
بازگشت