DocumentCode :
1212982
Title :
Power transformer resonance-measurements and prediction
Author :
Liu, Yilu ; Sebo, Stephen A. ; Caldecott, Ross ; Kasten, Donald G. ; Wright, Selwyn E.
Author_Institution :
Dept. of Electr. Eng., Ohio State Univ., Columbus, OH, USA
Volume :
7
Issue :
1
fYear :
1992
fDate :
1/1/1992 12:00:00 AM
Firstpage :
245
Lastpage :
253
Abstract :
The authors describe and summarize the results of impedance measurements of 12 converter transformers and 12 nonconverter transformers in the 50 Hz to 1 MHz frequency range. Impedance characteristics associated with various parameters are discussed. Studies of transformer winding first resonant frequencies and prediction equations are presented. Many conditions are represented: single and three-phase transformers, different core and winding designs, high voltage and low voltage windings, and various terminations. From measured driving point impedance, it can be clearly seen that the profile of impedance changes both in terms of magnitude and phase angle as a function of frequency. The first resonant frequency is found at the first zero crossing of the phase angle. The highest value found was 80 kHz
Keywords :
electric impedance measurement; power transformers; resonance; 50 Hz to 1 MHz; converter transformers; impedance measurements; nonconverter transformers; power transformers; resonance; resonant frequency; single-phase transformers, 3-phase transformers; transformer cores; transformer windings; Equations; Frequency conversion; Impedance measurement; Low voltage; Phase transformers; Power transformers; Resonance; Resonant frequency; Transformer cores; Windings;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.108914
Filename :
108914
Link To Document :
بازگشت