• DocumentCode
    1212982
  • Title

    Power transformer resonance-measurements and prediction

  • Author

    Liu, Yilu ; Sebo, Stephen A. ; Caldecott, Ross ; Kasten, Donald G. ; Wright, Selwyn E.

  • Author_Institution
    Dept. of Electr. Eng., Ohio State Univ., Columbus, OH, USA
  • Volume
    7
  • Issue
    1
  • fYear
    1992
  • fDate
    1/1/1992 12:00:00 AM
  • Firstpage
    245
  • Lastpage
    253
  • Abstract
    The authors describe and summarize the results of impedance measurements of 12 converter transformers and 12 nonconverter transformers in the 50 Hz to 1 MHz frequency range. Impedance characteristics associated with various parameters are discussed. Studies of transformer winding first resonant frequencies and prediction equations are presented. Many conditions are represented: single and three-phase transformers, different core and winding designs, high voltage and low voltage windings, and various terminations. From measured driving point impedance, it can be clearly seen that the profile of impedance changes both in terms of magnitude and phase angle as a function of frequency. The first resonant frequency is found at the first zero crossing of the phase angle. The highest value found was 80 kHz
  • Keywords
    electric impedance measurement; power transformers; resonance; 50 Hz to 1 MHz; converter transformers; impedance measurements; nonconverter transformers; power transformers; resonance; resonant frequency; single-phase transformers, 3-phase transformers; transformer cores; transformer windings; Equations; Frequency conversion; Impedance measurement; Low voltage; Phase transformers; Power transformers; Resonance; Resonant frequency; Transformer cores; Windings;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.108914
  • Filename