DocumentCode :
1213016
Title :
Modified Hopf bifurcation index for power system stability assessment
Author :
Tomim, M.A. ; Lopes, B.I.L. ; Leme, R.C. ; Jovita, R. ; De Souza, A. C Zambroni ; de Carvalho Mendes, P.P. ; Lima, J.W.M.
Author_Institution :
Dept. of Electr. Eng., Univ. Fed. de Hajuba, Brazil
Volume :
152
Issue :
6
fYear :
2005
Firstpage :
906
Lastpage :
912
Abstract :
An index to identify Hopf bifurcation points in power systems is proposed. Two models are used to exploit the method. When the network dynamics are modelled, systems susceptible to subsynchronous resonance are identified. On the other hand, if interactions between the network and generators are not the focus, Hopf bifurcations may be identified as a consequence of generator oscillations. The index proposed is based on the calculation of a reduced set of eigenvalues, rendering the technique effective even for large power systems. Additional analysis is carried out for two techniques previously proposed in the literature, which are based on the calculation of the least singular value of an augmented system matrix, and on its least eigenvalue.
Keywords :
bifurcation; eigenvalues and eigenfunctions; matrix algebra; oscillations; power system stability; subsynchronous resonance; augmented system matrix; eigenvalues; generator oscillation; large power system; least singular value; modified Hopf bifurcation index; network dynamics; power system stability; subsynchronous resonance;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20045159