DocumentCode :
1214155
Title :
An investigation of breakdown voltage with small arc current due to poor contact in SF6 gas
Author :
Sugiyama, Shuichi ; Morita, Tadashi ; Hosokawa, Tatsuzo ; Sekiya, Yoshihisa ; Mukaiyama, Yoku ; Takagi, Isao ; Lee, Kwang-Sik
Author_Institution :
Fuji Electr. Corp. R&D Ltd., Kawasaki, Japan
Volume :
7
Issue :
1
fYear :
1992
fDate :
1/1/1992 12:00:00 AM
Firstpage :
332
Lastpage :
338
Abstract :
Using an experimental apparatus modeled for the contact portion of a gas insulated switchgear (GIS), the influence of the distance between the portion and the dead tank of the GIS and arc duration on the breakdown voltage was investigated. The study was conducted both experimentally and theoretically for the case when the arc was ignited in the portion. In the theoretical analysis, profiles of flow velocity and gas density were calculated. Breakdown voltage evaluated through the gas density was in relatively good agreement with that of the experiment
Keywords :
arcs (electric); electric breakdown of gases; gaseous insulation; sulphur compounds; switchgear; SF6; arc current; breakdown voltage; flow velocity; gas density; gas insulated switchgear; Breakdown voltage; Contact resistance; Electrodes; Gas insulation; Geographic Information Systems; Ignition; Research and development; Resistance heating; Samarium; Switchgear;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.108926
Filename :
108926
Link To Document :
بازگشت