DocumentCode :
12152
Title :
On Topology Attack of a Smart Grid: Undetectable Attacks and Countermeasures
Author :
Jinsub Kim ; Lang Tong
Author_Institution :
Sch. of Electr. & Comput. Eng., Cornell Univ., Ithaca, NY, USA
Volume :
31
Issue :
7
fYear :
2013
fDate :
Jul-13
Firstpage :
1294
Lastpage :
1305
Abstract :
Covert data attacks on the network topology of a smart grid is considered. In a so-called man-in-the-middle attack, an adversary alters data from certain meters and network switches to mislead the control center with an incorrect network topology while avoiding detections by the control center. A necessary and sufficient condition for the existence of an undetectable attack is obtained for strong adversaries who can observe all meter and network data. For weak adversaries with only local information, a heuristic method of undetectable attack is proposed. Countermeasures to prevent undetectable attacks are also considered. It is shown that undetectable attacks do not exist if a set of meters satisfying a certain branch covering property are protected. The proposed attacks are tested with IEEE 14-bus and IEEE 118-bus system, and their effect on real-time locational marginal pricing is examined.
Keywords :
IEEE standards; power meters; power system economics; pricing; smart power grids; IEEE 118-bus system; IEEE 14-bus system; control center; data topology attack; heuristic method; man-in-the-middle attack; marginal pricing; network data switching; power meter; smart grid; undetectable attack; Malicious data attack; SCADA system; bad data detection; cyber physical system security; power system state and topology estimation;
fLanguage :
English
Journal_Title :
Selected Areas in Communications, IEEE Journal on
Publisher :
ieee
ISSN :
0733-8716
Type :
jour
DOI :
10.1109/JSAC.2013.130712
Filename :
6547837
Link To Document :
بازگشت