Statistical Property of Breakdown between Electrode and Shield in High-Voltage Vacuum Interrupter
Author :
Toya, H. ; Hayashi, T. ; Shinozaki, Y. ; Murai, Y.
Volume :
13
Issue :
5
fYear :
1985
Firstpage :
311
Lastpage :
314
Abstract :
Statistical property of the breakdown between stainless or copper electrode and stainless arc shield is studied by applying (250 × 2000)-¿s switching impulses to model vacuum interrupters. Higher breakdown voltages are obtained in negative polarity than in positive polarity. The effective area of breakdown which takes the electric-field distribution on the anode surface into account is introduced to explain the polarity effect of breakdown voltage using Weibull statistics.
Keywords :
Anodes; Breakdown voltage; Coaxial components; Copper; Electric breakdown; Electrodes; Interrupters; Steel; Vacuum arcs; Vacuum breakdown;